Description
| Isolated Ground Receptacle Type | Flush Receptacles |
| Wiring Scheme | 2 Pole, 3 Wire Grounding |
| Amperage | 15 Amp |
| Voltage | 125 Volts |
| Color | Orange |
| Face Style | Finder Groove |
| NEMA designation | 5-15R |
| Horse Power | 0.5 |
| Wire Clamp | .062" (1.6) Steel - Ni Plated |
| Terminal Screw | #8-32 Brass |
| Ground Screw | #8-32 Brass (Green) |
| Top Material | Nylon |
| Base Material | Reinforced PET |
| Power Contacts Material | .037" Phosphor Bronze |
| Mounting Strap (Bridge) | .05" Brass |
| Rivet Material | Brass |
| Auto Ground Clip | Stainless Steel |
| Mounting Screw Material | Steel-Zinc Plated |
| Product ID | Ratings permanently molded on device |
| Dielectric Voltage Withstand | 2,000V Minimum |
| Current Interrupting | Certified for current interrupting at full rated current. |
| Temperature Rise | Max 30°C temperature rise at full rated current after 50 cycles of overload at 150% of rated current at a power factor of 75%. |
| Terminal Accommodation | #14-#10 AWG copper stranded or solid conductor only |
| Terminal ID | In accordance with UL 498 (X, Y, Z, White, Green) |
| Flammability | UL 94 V2 or better. |
| Operating Temp. | Maximum continuous 75 deg. C; Minimum -40 deg C (without impact) |
| Certifications | UL Listed, CSA Approved |